Siemens Photo Resistive Flame Detectors QRB1 Series

Siemens QRB1 Series photoresistive flame detectors monitor yellow-burning oil flames by sensing visible light radiation. With peak spectral sensitivity near 600 nm, they provide flame signals to compatible Siemens LAL, LME7, LMO, LMV and LOA burner controllers. Available in several sensitivity and mounting configurations, QRB1 detectors are intended for intermittent-operation oil burners, industrial boilers and heating systems.

Product Description

Siemens QRB1 Series Photoresistive Flame Detectors for Oil Burners

Siemens QRB1 Series photoresistive flame detectors are designed to supervise yellow-burning oil flames using radiation in the visible-light spectrum. A light-sensitive resistor responds to flame illumination, enabling the connected burner controller to evaluate flame presence.

Primarily intended for oil burners operating intermittently, QRB1 detectors can receive light from the front or at a 90-degree lateral angle. They are used in industrial boiler installations, oil-fired burner assemblies and heating equipment.

Key Features

  • Designed for flame supervision of yellow-burning oil
  • Photoresistive flame detection principle
  • Peak spectral sensitivity of approximately 600 nm
  • Frontal and 90-degree lateral flame illumination
  • Normal, high and selected-high sensitivity variants
  • Flange-and-clamp or flexible plastic plug mounting options
  • Compact sensing assembly with an integrated two-core cable
  • IP40 ingress protection

Compatible Siemens Burner Controls

The QRB1 family is intended for use with specified models from the following Siemens burner control families:

  • Siemens LAL Series
  • Siemens LME7 Series
  • Siemens LMO Series
  • Siemens LMV Series
  • Siemens LOA Series

Industrial Applications

  • Oil-fired burner systems
  • Industrial boiler combustion equipment
  • Industrial heating installations
  • Intermittently operated oil combustion systems

Selection and Installation Guidelines

Before selecting a Siemens QRB1 detector, confirm its complete model designation, required sensitivity, connection cable length, termination arrangement, mounting hardware and compatibility with the installed burner control.

Important: External illumination, including sunlight and boiler room lighting, may influence flame detection. Correct positioning, installation and commissioning tests must be completed by qualified technicians in accordance with the applicable burner control documentation.

Specifications

Siemens QRB1 Series Photoresistive Flame Detector Technical Specifications

ManufacturerSiemens
Product FamilyQRB1 Series
Detector ClassificationPhotoresistive Flame Detector
Sensing TechnologyPhoto Resistor
Applicable FlameYellow-Burning Oil Flames
Optical Detection SpectrumVisible Light Spectrum
Peak Spectral SensitivityApproximately 600 nm
Operating DutyIntermittent Operation
Flame Viewing DirectionFrontal or Lateral (90°)
Detector Sensitivity OptionsNormal / High / Selected High
Housing Identification ColorsNormal: Black
High: Red
Selected High: Blue
Ingress ProtectionIP40
Electrical Safety ClassClass II
Integrated Detector CableStranded Copper Wire, 2 x 0.75 mm²
PVC Jacket, 5.2 mm Diameter
Connection Cable LengthDepending on Model
Ambient Operating Temperature-20 to +60°C
Permissible Relative HumidityBelow 95% RH
Maximum Installation Elevation2,000 m Above Sea Level
Mounting OrientationOptional
Approximate Weight20–35 g, Depending on Model
Mounting ConfigurationsQRB1...A: Flange and Clamp
QRB1...B: Soft Plastic Plug
Compatible Siemens Burner ControlsLAL, LME7, LMO, LMV, LOA

Technical Note: Sensitivity, cable length, electrical termination and mounting accessories depend on the exact detector version. Confirm the applicable specifications before ordering.