- Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor tube checking function.<br>
- Can be mounted horizontally, vertically or at any angle in between.<br>
- The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism.<br>
- Field replaceable ultraviolet sensing tube and quartz viewing window.<br>
- Models with threaded conduit fitting and color-coded leadwires allow rapid electrical installation.<br>
- C7061A1046 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell.<br>
- Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.<br>
- Protective heat block built into mounting flange.<br>
- -40°F (-40°C) rated ultraviolet sensing tube is supplied.<br>
- C7061E meets NEMA 4 standards with viewing window rated to 20 psi.<br>
- C7061F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi.<br>
- Pipe connection (all models) 1 in. NPT, includes 1 in. to 3/4 in. bushing adapter for 3/4 in. viewing pipe mounting.)